Conventional MULTI Detector
Specifications
Operating Voltage Range: 9 to 28VDC Volts Non-polarized
Standby Current: ≤60μA @ 24 VDC
Maximum Alarm Current (LED on: ) ≤30mA @ 24 VDC
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 14°F to 120°F (-10°C to 49°C)
Description
The device is a photoelectronic detector that uses a state of the art optical sensing chamber. This detector is designed to provide open area protection and to be used with most conventional fire alarm control panel. Two LEDs on each detector provide local 360° visible alarm indication. They flash every 3~5 seconds indicating that power is applied and the detector is working properly. The LEDs latch on in alarm. LEDs will be off when a trouble condition exists indicating that the detector sensitivity is outside the listed limit. The alarm can be reset only by a momentary power interruption.